Low Temperature R22 Air Cooled Water Chiller 71kW COP 3.68 380V 50Hz

Categories Air Cooled Modular Chiller
Brand Name: EuroKlimat
Model Number: EKAC 250BRLH
Certification: ISO9001, ISO14001, OHSAS18001, CRAA, CQC
Place of Origin: China
MOQ: 1
Price: negotiation
Payment Terms: L/C, T/T
Supply Ability: 50 pcs per month
Delivery Time: 20 working days after received your payment
Packaging Details: Carton
Product Name: Low-temp high-efficiency model Air-cooled Heat Hump Unit
Limiting Temperature: -20 ℃ Cooling and 48℃ Heating
Heating Capacity range: 75-1200
Cooling Capacity range: 71 kW-1136 KW
COP: 3.68
IPLV: 4.33
  • Haven't found right suppliers
  • Our buyer assistants can help you find the most suitable, 100% reliable suppliers from China.
  • And this service is free of charge.
  • we have buyer assistants who speak English, French, Spanish......and we are ready to help you anytime!
  • Submit Buying Request
    • Product Details
    • Company Profile

    Low Temperature R22 Air Cooled Water Chiller 71kW COP 3.68 380V 50Hz


    71kW COP 3.68 Low-temp high-efficiency model air cooled modular chiller / heat pump unit


    Specifications:


    Technical data sheet


    Model EKAC 250BRLHEKAC 500BRLHEKAC 750BRLHEKAC 1000BRLHEKAC 1250BRLHEKAC 1500BRLH
    Unit combinationMaster unitEKAC 250BRLHMEKAC 250BRLHMEKAC 250BRLHMEKAC 250BRLHMEKAC 250BRLHMEKAC 250BRLHM
    slave unit--EKAC 250BRLHS2EKAC 250BRLHS3EKAC 250BRLHS4EKAC 250BRLHS5EKAC 250BRLHS
    Nominal cooling capacitykW71142213284355426
    USRT20.1940.3860.5780.76100.95121.14
    ×104kcal/h6.1012.218.324.430.536.6
    Nominal heating capacitykW75150225300375450
    USRT21.3342.6663.9985.32106.65127.98
    ×104kcal/h6.4512.919.3525.832.2538.7
    Total power of nominal cooling capacitykW19.338.657.977.296.5115.8
    Total power of nominal heating capacitykW20.0406080100120
    Power supply 380V/3N~/50Hz
    RefrigerantType R22
    Control Electronic expansion valve
    CompressorType Fully hermetic volute compressor
    Lubricant Mineral oil (SUNISO 3GS)
    Qty.Set24681012
    FanType High-efficiency vacuum braze-welded panel type
    Qty.Set24681012
    Water side heat exchangerType High-efficiency vacuum braze-welded panel type
    Water flow for
    cooling
    3
    m /h
    12.224.436.648.86173.2
    Water flow rate in
    heating mode
    3
    m /h
    12.925.838.751.664.577.4
    Water resistancekPa363636363636
    Recommended diameter for general inlet/outlet water pipeinch≥2≥3≥3≥4≥4≥5
    Power cable specificationSection area of live line2
    mm
    ≥10≥35≥70≥95≥120≥150
    Qty. of live lines 3
    Section area of null line2
    mm
    ≥4
    Qty. of null lines 1
    Section area of grounding line2
    mm
    ≥10≥16≥35≥50≥60≥75
    Qty. of grounding lines 1
    DimensionsL x Hmm2012×1840
    Widthmm88021253370461558607105
    Unit weightNet weightkg59011801770236029503540
    Operating weightkg60012001800240030003600

    Note:
    ■ Test conditions for nominal cooling capacity: outlet water temperature 7°C; water flow: 0.172m3/(h·kw); outdoor ambient temperature 35°C.
    ■ Test conditions for nominal heating capacity: outlet water temperature 45°C; water flow: 0.172m3/(h·kW); outdoor dry/web bulb temperature
    7°C/6°C.
    ■ Water resistance at the air conditioner side includes water pressure drop of the unit and the attached Y-shaped filter.
    ■ Main Pipes of combined units need to be customized and installed on site. The diameter of the pipes must meet design requirements. EK
    does not provide the pipes.
    ■ Modular units can be formed using the 1 - 16 basic modules of same type or of different types as per practical needs. The above table lists
    the parameters for common module combinations.
    ■ For on-site electric wiring, see the name plate or installation menu of the unit.


    Decription


    1. The low-temperature high-efficiency modular air cooled heat pump unit features a full-load COP up to 3.68, meeting the national standard for tier-1 energy saving products (3.4). Both the cooling and heating energy efficiency of the low-temperature high efficiency modular air-cooled heat pump unit is greatly improved to save operation cost for customers (value added). The energy efficiency is especially excellent with partial workload, bringing comfort to customers at much lower cost.

    2. The EKAC low-temperature high-efficiency unit features leading-edge EVI (Enhanced Vapor Injection) compressors, increasing refrigerant recycling by as much as 20%. The evaporation capacity is improved by mid-pressure refrigerant intake. One compressor compresses refrigerant 2 times in each cycle. Half-M fins are used to improve the heat-exchange efficiency of the heat exchanger. The unit features state-of-the-art cross diagonal convection angles for stainless steel braze-welded panel-type heat exchanger and stainless steel braze welded panel-type economizer (used to increase the enthalpy differentiation between the inlet and outlet of the evaporator). An EXV is used to precisely control the operation of the unit.

    3. The EKAC low-temperature high-efficiency modular air-cooled heat pump unit features excellent heating COP when the ambient temperature is low (20% higher than common air-cooled heat pump unit when the ambient temperature is -10°C). The lower ambient temperature limit is expanded from -10°C of common units to -20°C. This greatly improves cooling performance in areas where the winter is cold, reducing or eliminating the need for auxiliary heaters

    4. Each modular unit has two power gears. When multiple modular units are combined, there could be many power gears. When working at a partial workload (99% of the operation time), the unit intelligently regulates the output based on the actual workload, making the operation efficiency even higher. With an optional 2-way valve water control feature, the unit can send out signals to cut off chilled water. This enables automatic flow control for pumps in line with the transducer, which helps save more energy.

    5. Currently, centralize heating by using heat pipes are very common. This type of heat provision wastes a lot of heat in the heating pipes, and is low in efficiency. Other defects include fixed heating period, environment pollution, difficult to maintain and collection fees, and not meeting national requirements on energy saving. The EKAC low-temperature high-efficiency modular air-cooled heat pump unit can provide enough heat in an ambient temperature as low as -20°C. The heating period, output capacity, and indoor temperature can be flexibly conditioned as required by the customer. The unit provides both heating and cooling functions, saving installation and maintenance costs. Unit of this series meets the trend for energy saving technologies, and is revolutionary compared with traditional heat provision solutions.