Sign In | Join Free | My uabig.com |
|
Categories | Electrical Test Instrument |
---|---|
Brand Name: | AI |
Model Number: | CBA-I |
Certification: | ISO9001 |
Place of Origin: | China |
MOQ: | 1 set Circuit Breaker Timing Test Set |
Price: | Negotiable |
Payment Terms: | Western Union, T/T, L/C |
Supply Ability: | 100 sets/motnh |
Delivery Time: | 15 days |
Packaging Details: | Circuit Breaker Timing Test Set packed in veneer case |
Functions: | measuring contact resistance, arcing contacts and vibration characteristics etc |
Test object: | power system circuit breakers, mechanical characteristics of load switches ,isolated switchea,AC high voltage switches |
Time test: | 0 to 4000ms |
Distance test: | 0-250mm |
Pre-insertion resistance measurement: | 50~5000ohm |
Test current: | 25~100A |
Vibration measurement: | 0~5000G |
Warranty: | 1 year |
Company Info. |
Advanced Instruments Co.,Limited |
Verified Supplier |
View Contact Details |
Product List |
Introduction:
Major Testing Parameters and Functions:
Specifications:
1 | 12 channels for time measurement | 3-channel support both the time contact and resistance contact time 6-channel isolated contacts for cascaded unit measurement of pole |
2 | Time measurement | Range: 4000ms; Error :< 0.1ms; Resolution: 0.01ms |
3 | Travel measurement according to sensor | Linear resistance sensor: Measurement range: 0~250mm; resolution: 0.01mm; error: <0.5mm Measurement range: 0~25mm; resolution: 0.01mm; error: <0.05mm Angle resistance sensor: Measurement range: 0~360°; resolution: 0.01°; error: <0.5° |
4 | Pre-insertion resistance measurement | Range: 50~5000ohm; error :<1%RDG+2D |
5 | Dynamic resistance measurement | Test current: 25~100A, Measurement error :< 1%RDG+2D |
6 | Contact resistance measurement | Range:0--10mohm, Error <0.5%RDG+0.05%FS Range: 0-2mohm, Error: <0.5%RDG+2D |
7 | Speed measurement | 250mm linear resistance scale: 0~20m/s; error: <0.5%RDG+2D 25mm linear resistance scale: 0~20m/s; error: <0.5%RDG+2D Angle sensor: 0~20m/s; error: <0.5%RDG+2D Acceleration sensor: 0~20m/s; error: <5%RDG+2D |
8 | Coil current measurement | Range: 0~20A; resolution: 0.001A; error: <0.01A |
9 | Vibration measurement | Range: 0~5000G; error: <3% |
10 | Internal DC power source | voltage: 12~265V; current:0~20A |
11 | Data transaction | Built-in 8G storage memory and 2 USB interface for data export and external keyboard or mouse connection |
12 | Power supply | AC220V±10%; 50Hz±10% |
13 | Working environment | -10~50°C; Humidity: <80% |
![]() |